Inputs:
- Supply air temperature sensor
- Mixed air temperature sensor
- Return air temperature sensor
- Outdoor air temperature sensor
- Humidity sensor
- CO2 sensor
- Fan status switches
- Heating/cooling valve status switches
Outputs:
- Supply air damper actuator
- Return air damper actuator
- Mixing box damper actuator
- Heating coil control valve actuator
- Cooling coil control valve actuator
- Fan motor control relay
- Alarm and fault signal outputs
Control sequence:
- The controller reads the input signals from the various sensors to determine the current conditions in the system.
- If the outdoor air temperature is below a certain setpoint and the humidity level is within acceptable limits, the controller opens the economizer damper and allows outside air to be used for cooling instead of mechanical cooling.
- The controller adjusts the supply air damper position based on the required airflow rate and static pressure setpoints.
- The controller adjusts the return air damper position to maintain neutral pressure in the space being served.
- The controller adjusts the mixing box damper position to ensure proper mixing of the outside and return air streams.
- If the supply air temperature is below the desired setpoint, the controller modulates the heating coil valve to increase the supply air temperature.
- If the supply air temperature is above the desired setpoint, the controller modulates the cooling coil valve to decrease the supply air temperature.
- If the humidity level is too high or too low, the controller adjusts the operation of any humidification or dehumidification components to maintain the desired humidity setpoint.
- If the CO2 level is too high, the controller increases the ventilation rate to bring in more outside air.
- The controller monitors the status of the fans and heating/cooling valves and triggers alarms or fault signals if any issues are detected.
Sequence of Operation for Air Handling Units